1 Installation Manual & Set-Up Guide Ordinary Area ITAS Ambient Sensing Control Panel ITAS-EXT Ambient Sensing Extender Control Panel ITLS Line Sensing Control Panel ITLS-EXT Line Sensing Extender Control Panel Hazardous Area ITASC1D2 Ambient Sensing Control Panel ITASC1D2-EXT Ambient Sensing Extender Control Panel ITLS C1D2 Line Sensing Control Panel ITLS C1D2-EXT Line Sensing Extender Control Panel PK497-1 0037-75514 1 June 2013

2 Safety Precautions Important Safeguards Throughout the intelliTRACE Setup Guide, these sym- To avoid electrical shock or injury, always remove pow- bols will alert you to potential hazards. Safety precau- er before servicing a circuit. Personnel working with tions should always be followed to reduce the risk of or near high voltages should be familiar with modern fire, electrical shock, injury and even death to persons. methods of resuscitation. Contact an area supervisor or safety personnel for more information. Please read all instructions before operating your intelliTRACE ITLS, ITAS, ITLS-EXT or ITAS-EXT Con- trol Panel. WARNING WARNING ELECTRIC SHOCK HAZARD HIGH VOLTAGE is used in the opera- Any installation involving control tion of this equipment; DEATH ON equipment must be performed by a CONTACT may result if personnel fail qualified person and must be effec- to observe safety precautions. tively grounded in accordance with the National Electrical Code to elimi- nate shock hazard. Learn the areas containing high-volt- age connections when installing or operating this equipment. Be careful not to contact high-volt- age connections when installing or operating this equipment. Before working inside the equipment, turn power off and ground all points of high potential before touching them. ii

3 Table of Contents Contents Page Number Safety Precautions..................................................................................................................................................ii Table of Contents...................................................................................................................................................iii Introduction............................................................................................................................................................. 1 Model Overview...................................................................................................................................................... 2 Theory of Operation............................................................................................................................................... 3 Before Powering Up........................................................................................................................................... 4 Main Menu Screen.................................................................................................................................................. 5 Owner Setup Menu................................................................................................................................................. 6 Security Levels & Password Screen..................................................................................................................... 7 Setpoints Tab.......................................................................................................................................................... 8 Apply Settings Globally.......................................................................................................................................... 9 Tuning Tab............................................................................................................................................................. 10 Control Modes: ON/OFF, Autotune & PID......................................................................................................... 11 Soft Start Feature................................................................................................................................................. 11 I/O (Sensor & Output) Mapping........................................................................................................................... 12 Sensor Mapping................................................................................................................................................... 12 Output Mapping.................................................................................................................................................... 13 Increasing the Number of Inputs per Output..................................................................................................... 14 System Properties................................................................................................................................................ 15 Auto Cycle Feature............................................................................................................................................... 16 Communications.................................................................................................................................................. 17 Remote Monitoring & System Management...................................................................................................... 17 Event Log.............................................................................................................................................................. 18 Faults (Alarms)...................................................................................................................................................... 19 Clearing Alarms.................................................................................................................................................... 19 Alarm Troubleshooting......................................................................................................................................... 20 Extension Panels Connection & Considerations............................................................................................ 21 Connecting the Extension panel to the Main Panel.......................................................................................... 21 Extension Panel Considerations......................................................................................................................... 21 Service Contact Information............................................................................................................................... 22 Appendix............................................................................................................................................................... 23 Panel Specifications............................................................................................................................................. 23 Default Settings.................................................................................................................................................... 23 Standard Order Tables......................................................................................................................................... 24 ITLS Line Sensing: 6 36 Loops, Non-Hazardous Environment.................................................................. 24 ITLS-EXT Extender Panel for the ITLS............................................................................................................. 26 ITAS Ambient Sensing: 6 36 Loops, Non-Hazardous Environment........................................................... 28 ITAS-EXT Extender Panel for the ITAS............................................................................................................ 30 ITLSC1D2 Line Sensing, Class I, Division 2:................................................................................................... 32 ITLSC1D2-EXT Extender Panel for the ITLSC1D2, Class I, Div 2.................................................................. 34 ITASC1D2 Ambient Sensing, Class I, Division 2:............................................................................................ 36 ITASC1D2-EXT Extender Panel for the ITASC1D2, Class I, Div 2.................................................................. 38 ModBus Specification.......................................................................................................................................... 40 iii

4 Introduction For nearly 100 years, customers have relied upon Chromalox for premiere quality and innovative solutions for industrial heating applications. Chromalox manufactures the worlds largest and broadest line of electric heat and control products. The intelliTRACE itls, itas, itlsc1d2 & itasc1d2 Series Multiple Loop Panels and Extender Panels are a complete temperature control and system management solution for electrical heat trace applications. They are designed for industrial applications in Hazardous (Class I, Division 2) or Non Hazardous Environments. intelliTRACE provides the user with a new, easy to navigate touch-screen interface, continuous built-in monitor- ing, off duty preventative maintenance, application flexibility and system customization. The ITAS and ITASC1D2 provide Ambient Sensing capabilities while the ITLS and ITLSC1D2 provide either Line Sensing or a hybrid function of both Line and Ambient Sensing capabilities. intelliTRACE Features: Hazardous (Class I, Division 2) or Non Hazardous Environments 10 VGA Touch Screen HMI (12 on Hazardous Environment Panels) 40 Amps/Loop @ 100 480 VAC SCR Control 6 Loops to 36 Loops Expandable to 72 Loops with Matching Extension Panels NEMA 4 Enclosure (Optional NEMA 4X 304 SS) Integral Circuit Panel with Circuit Breakers & Optional Main Disconnect (non-hazardous only) Soft Start Feature Full Communications Enhanced Data Logging Full Alarm Capabilities Complete GFEP Monitoring & Alarms Load Monitoring & Alarms UL, cUL Listing (CE is available) Touch Screen Computer: 6 Loops displayed / screen Quick launch to any 6 loop group, Setup Menu or System Screens Remote Desktop Monitoring Full User Setting Capabilities Baud rate, set points, units, alarms, etc. Specific Loop Naming/Identification Options: Fully Customizable I/O (Sensor & Output) Mapping (ITLS, ITLSC1D2 only) Enclosure Heater Wireless Communications 1

5 Model Overview The new line of intelliTRACE Panels provides a signifi- expansion needs. Simply connect the Extension Panel cant amount of application and feature flexibility. to its matching ITLS, ITLSC1D2 or ITAS, ITASC1D2 Base Panel and circuit capacity is seamlessly in- The ITAS and ITASC1D2 are designed for Ambient creased. The Extension Panels do not have a HMI, but Sensing applications while the ITLS and ITLSC1D2 are otherwise are identical. designed for Line Sensing applications. Additionally, the ITLS and ITLSC1D2 have the capability to func- These panels are UL and cUL Listed for Ordinary (Non tion as both a Line Sensing control panel and an Ambi- Hazardous) and Hazardous (Class I, Division 2) Envi- ent Sensing control panel should the Customizable I/O ronments. CE is available. Mapping feature be selected. Please see Table 1 below for applicable features and The intelliTRACE matching ITAS-EXT, ITASC1D2-EXT capabilities by model type. and ITLS-EXT, ITLSC1D2-EXT Extension Panels pro- vide the flexibility for the owner to meet their process Table 1 ITLS ITAS ITLS ITAS Standard Features/Capabilities ITLS C1D2 ITAS C1D2 ITLS-EXT C1D2-EXT ITAS-EXT C1D2-EXT Ordinary, Non-Hazardous Area X X X X Hazardous Area (Class I, Division II) X X X X 10 VGA Touch Screen HMI X X n/a n/a n/a n/a 12 VGA Touch Screen HMI (Class I, Div. II) X X n/a n/a n/a n/a 40 Amps/Loop @ 100 480 VAC X X X X X X X X Circuits 6, 12, 18, 24, 30, 36 SCR Control X X X X X X X X NEMA 4 Enclosure X X X X X X X X Integral Circuit Panel with Circuit Breakers X X X X Soft Start Feature X X X X 1 1 1 1 Full Communications X X X X 1 1 1 1 Enhanced Data Logging X X X X 1 1 1 1 Full Alarm Capabilities X X X X 1 1 1 1 Complete GFEP Monitoring & Alarms X X X X 1 1 1 1 Load Monitoring & Alarms X X X X 1 1 1 1 UL, cUL Listing X X X X X X X X Options Fully Customizable I/O Mapping X X n/a n/a 1 1 n/a n/a Enclosure Heater X X X X X X X X Wireless Communications X F X F 1 F 1 F Main Disconnect X n/a X n/a X n/a X n/a NEMA 4X 304 SS X X X X X X X X CE, FM and ATEX available X X X X X X X X X - Available as a standard or option for this model 1 - This feature is enabled when paired with matching base panel F - Future feature n/a - This feature is not available for this model 2

6 Theory of Operation The set-up of the individual and global loop parameters is explained in the Owner Set-up and Setpoints Tab sections of this manual. This Theory of Operation overview is intended to give a quick summary of how it all works together. Each loop of the system may be enabled (active) or disabled (inactive). A disabled loop will have no output and will not map into the common alarm. It will display Loop # and Loop Disabled text in the middle of the screen. Alarms for disabled loops will not be monitored or displayed on the screen. Each loop of the system may use unique individual control parameters or the control parameters may be alike. The Global Settings function facilitates this action. The GFEP and Load current are automatically and continuously being calculated. The horizontal yellow bar indicates the average output current for that circuit. The GFEP current value is not displayed on the screen but its value is compared to the GFEP setpoint. A GFEP alarm condition will occur when the GFEP current value exceeds the GFEP setpoint value. If a ground fault is detected during normal operation and Trip checkbox on the Setup screen is checked, the output of the defective loop is set to 0% and that loop goes into an alarm condition. If Trip checkbox is not checked, the operation of that loop continues and that loop goes into alarm condition. During extended periods of time where the output of all loops are off, such as during warmer seasons, the Auto Cycle feature may be engaged. This feature initiates ground fault and current testing. Each output is tested for one minute within the desired Auto Cycle Interval. The Auto Cycle feature may be disabled by setting the Auto Cycle Interval time to 0 Hours. To limit inrush current on the overall system, a proprietary Soft Start algorithm is applied during sys- tem start-up. This will ONLY occur while the operation mode is set to AUTO. The Soft Start program will increment output % by 1% every 1 second until the desired temperature is reached or the output % achieves 100%. After the Soft Start program completes its cycle, the Control Mode of the system will either be PID or ON/OFF Control Mode, depending what was selected by the user. The Soft Start Program will not function if the control mode is set to Manual. 3

7 Before Powering Up Chromalox takes great pride in knowing that we have provided to you a product of premium quality and workman- ship. We have taken every precaution to ensure that your equipment arrives safe and secure. However, vibration and temperature changes during shipping can cause some components to become loose. Additionally, throughout the life span of this product, other environmental and application conditions may have affected the mechanical and electrical continuity of several internal components. Therefore, for your safety and overall product performance, please take the time to familiarize yourself with the MAINTENANCE, OPERATION, AND INSTALLATION INSTRUCTIONS technical manual that was shipped with your panel. Since it is not uncommon for electrical wiring and mechanical connections to become slightly loosened during shipment, we ask that you pay particular attention to section 4-5.3 Wiring and Connections: 4-5.3 WIRING AND CONNECTIONS. Check wiring and connections as follows: a. Inspect wiring for wear, fraying, chipping, nicks, and evidence of over- heating. Repair minor defects with a good grade of electrical tape, or replace if needed. b. Inspect for loose electrical and mechanical connections. Tighten or replace defective crimp-style lugs. Re-solder loose solder connections. Tighten or replace all loose or missing hardware. 4

8 Main Menu Screen The ITAS/ITLS Touch Screen Computer is extremely user friendly and quite intuitive. Navigation to any other screens or any 6-Loop grouping of loops is accomplished by selecting the gray labeled buttons along the bottom of the screen or in the upper right or left hand corners. The main menu screen displays alarm status, loop number, loop name, process and set point temperatures, cur- rent load demand, manual/auto control state and output percentage for 6 loops at a time. See Figure 1. Figure 1 5

9 Owner Setup Menu The SETUP button at the bottom of the screen is a quick launch to the Setup Property Sheet which is simply a series of tabaulated screens. See Figure 2. Figure 2 Each Tab contains input cells for the panel operation. For example, temperature, current and override controls are located within the Setpoints tab. Likewise, one may navigate to any of the other tab categories from within the Setup Property Sheet. Navigation notes: 1. Each screen illustrates 6 loops at a time. To make setting changes to loops beyond the current screen within the Setpoints, Tuning, Sensor Mapping (if equipped) or Autocycle tabs, one must select the Loop Navigation buttons in the upper right or left of screen. 2. For most screens, to save your settings, select the OK button. To exit out, select the X button. 3. Auto Test is a Factory tab and is not available to the owner. 6

10 Security Levels & Password Screen After touching the SETUP button, but before the Setup Menu is presented, a pop-up screen requesting a pass- word will appear. See Figure 3: Figure 3 Initial factory set passwords for the below levels of Security are: LevelTitle Code 4. Manager 999 3. Engineering 55 2. Supervisor20 1. Operator 100 Enter the appropriate password and then hit OK to continue to the setup screen. Each of the above Security Levels has predefined accessibility and rights within the programming of the control panel. They include: LevelTitle Accessibility/Rights 4. Manager All customer pages, all passwords and Setpoints editing 3. Engineering All customer pages, Engineering password and All Setpoints editing 2. Supervisor Setpoints, Tuning and Sensor Mapping Tabs & All Setpoints editing 1. Operator Setpoints Tab. Temperature Set Point editing Changes to specific areas within the Setup Property Sheet can only be made once the correct security level code has been selected. 7

11 Setpoints Tab The Setpoints tab (See Figure 4) contains input cells for the following settings for each loop: Customized Naming of each Loop Process Temperature Set Point High & Low Temperature Alarm Limits High & Low Current Alarm Limits Maximum allowable GFEP (Ground Fault Equipment Protection) Alarm Limit Trip and/or Latch Enabled/Disabled (Output permission) upon GFEP Violation Output behavior, whether Automatically or Manually Manual Output Load Percentage (if enabled) Loop Output Override (Enable or Disable Each Loop) Additionally, there exists a Global Setting within the Loop# 1 Grid Apply Globally Setting Figure 4 8

12 Setpoints Tab Navigation notes: 1. Each screen illustrates 6 loops at a time. To make setting changes to loops beyond the current screen within the Setpoints Tab, one must select the Loop Navigation buttons in the upper right or left of screen. Figure 5 illustrates the input cell identification and location for a single loop within the Setpoints Tab: Figure 5 9

13 Definitions for each of the Setpoints Tab Input Cells: Name: Customize the Name of this individual circuit or loop Temp SP: Process Temperature Set Point (degrees F or C) HI SP: High Temperature Alarm Limit (degrees F or C) LO SP: Low Temperature Alarm Limit (degrees F or C) Current HI: High Current Alarm Limit (Amps) Current LO: Low Current Alarm Limit (Amps) GFEP: Maximum Allowable Leakage Current setpoint (milliamps) Trip (GFEP): Enabled: If the GFEP limit is met, the output will be 0%. Disabled: If the GFEP limit is met, the output is unaffected. Latch (GFEP): Enabled: If the GFEP limit is met, the alarm condition will remain until it is manually cleared. Disabled: If the GFEP limit is met, the alarm condition will be cleared once the GFEP variable is less than the GFEP setpoint Auto/Manual: Select Auto if you wish the Output behavior to be a function of a PID Algorithm or ON/OFF Control (See Tuning Tab for selection) Select Manual if you wish the Output to be driven by a pre-determined Output Percentage. Enter the desired % output. Disable Output: Select this check box if you wish to turn off or disable this loop. Apply Globally: This allows the user to copy all of the settings or Loop Parameters from Loop #1 to all other available Loops. Apply Settings Globally The ITLS/ITAS has a feature which allows the user to apply settings from a single loop to all of the remaining loops within the system. Within Loop #1 on the Setpoints Tab (See Figure 4), complete the input of the parameters and select the Apply Globally button to mirror these settings across all loops. 10

14 Tuning Tab The owner has a choice of how the output is to be operated: Auto, Manual or Off. These selections are made within the Setpoints Tab. If Auto, or Automatic Control Operation is desired, then the tuning of the automatic control is accomplished via the Tuning Tab. See Figure 6. Figure 6 Control Modes: ON/OFF, Tuning Tab Navigation Autotune & PID Notes: Select ON/OFF if you wish the operation of the heat- 1. Each screen illustrates 6 loops at a time. To make ers to be 100% ON when a demand for heat exists setting changes to loops beyond the current screen and 0% once the Set Point Temperature of the pro- within the Tuning tab, one must select the Loop Nav- cess is achieved. igation buttons in the upper right or left of screen. Select PID if you desire PID control of the heaters. The owner may input his/her Integral, Derivative and Proportional Band parameters in the appropriate cells. However, if the Autotune Feature is selected, then the PID parameters will be calculated and entered by the system once the Autotune function has com- pleted its demand profile function. 11

15 Soft Start Feature These control panels are ideal for controlling heat trace The soft start program will not function if the control cable. Certain heating cables exhibit inherent current mode is set to Manual. inrush in colder temperatures. This inrush can cause nuisance breaker tripping. To limit inrush current on The default setting of the proprietary soft start feature the overall system, a proprietary soft start algorithm is for each circuit is enabled. However, the soft start applied during system start-up. This will ONLY occur feature may be disabled if so desired by the owner. while the operation mode is set to AUTO. The owner has the option to manage the soft start fea- ture on each circuit individually. The soft start program will increment output % by 1% every 1 second until the desired temperature is See Figure 6. reached or the output % achieves 100%. After the soft start program completes its cycle, the control mode of the system will either be PID or ON/OFF Control Mode, depending what was selected by the user. I/O (Sensor & Output) Mapping When factory enabled, the ITLS and ITLSC1D2 mod- This does not apply when only 1 Input/Circuit selection els provide the owner with customizable I/O mapping. is made from the Order Table. This becomes a very powerful and desirable feature when the owner needs added flexibility in controlling Multiple Sensor Mapping the circuit outputs beyond the standard single sensor A single sensor may be used independently or com- input. (This is not available in the ITAS or ITASC1D2 bined with other sensors to control more than one cir- models). cuit. For Example: There are two different types of I/O mapping: Sensor The average temperature of Sensors 1, 3 and 5 Mapping and Output Mapping. is used to control Circuit 1 while simultaneously 1. Sensor Mapping is the assignment of one or more the maximum Temperature of Sensor 3, 4 and 5 is Sensor Inputs to one or more output circuits. used to control Circuit 2. 2. Output Mapping is the assignment of one or more Combining Sensing Types Power Outputs to one or more output circuits. The owner may need to have multiple line and/or am- bient sensing control scenarios occurring simultane- Sensor (Input) Mapping and Output (Power) Mapping ously. are accessed via the I/O Mapping Tab found within the Setup Property Sheet. For example, these may be occurring simultaneously: 1. Circuits 1, 2, 3, 4, and 5 are all controlled by a single Sensor Mapping RTD (Sensor 1) that is sensing the ambient temper- ature (Ambient Sensing) Ambient or Line Sensing, Single Sensor A single sensor (RTD) may be mapped (or linked) to 2. Circuit 6 is controlled by Sensor Input 2 which is multiple output circuits. This allows several circuits to strapped to a process pipe. (Line Sensing) be controlled by a single sensor. Sensor mapping is accomplished within the I/O Map- Minimum, Maximum, Averaging ping Tab found in the Setup Property Sheet. See Fig- Several sensors may be mapped to a single output cir- ure 7. cuit. This allows a single circuit to be controlled by the minimum, or the maximum or the average temperature of all of the sensors mapped to that output circuit. This may be desirable on long runs or zones which realize varying temperatures or weather conditions at different times of the day. 12

16 Figure 7 Output Mapping This does not apply when only 1 Input / circuit selec- tion is made from the order table. Output Power Sensing Multiple Output Mapping A single output demand value may be mapped to mul- A single output demand value may be used indepen- tiple circuits. This allows several circuits to be con- dently or combined with other output demand values trolled by a single output demand value. to control more than one circuit. Minimum, Maximum, Averaging For Example: Several output demand values may be mapped to a The average output demand value of circuits 1, 3 single output circuit. This allows that circuit to be con- and 5 is used to control Circuit 1 while simultane- trolled by the minimum, or the maximum or the aver- ously the maximum output demand value of Cir- age output demand value of all of the outputs that are cuits 3, 4 and 5 is used to control Circuit 2. mapped to that single circuit. 13

17 Output Mapping is accomplished within the I/O Mapping tab found in the Setup Property sheet. See Figure 8. Figure 8 Increasing the Number of Inputs Per Output The Inputs/Circuit Code selection within the Order Table (see Appendix) determines the amount of available In- puts. The table below illustrates the Inputs/Circuit by panel design. Please note that the MAXIMUM number of Inputs for any ITLS or ITLSC1D2 System is 72. Total Number of Available Inputs Per Panel Design Number of Circuits Inputs / Circuit Code from Order Table in The Panel 1 2 3 6 6 12 18 12 12 24 36 18 18 36 54 24 24 48 72 30 30 60 Consult Sales 36 36 72 Consult Sales 14

18 System Properties Several informative items and general settings are Here, one can enter/revise the Facility Name, Date, available within the System tab. Time, Temperature Units, Auto Cycle Interval and Se- curity Codes. The Manager has access to all security The System tab is only available to the two highest codes while the Engineer has access to only the Engi- owner security levels: Manager and Engineer. neering Security Code. See Figure 9. Figure 9 The Autocycle function is reviewed in the Autocycle The Security Passwords and the respective rights for Feature section. each security level are reviewed in the Security Level and Password Screen Section above. 15

19 Auto Cycle Feature During prolonged down time periods, typically during On a sequential circuit basis, the Autocycle feature pe- the summer months, it advisable to intermittently exer- riodically monitors system performance between 1-999 cise the loops. This exercising of the loops is accom- hours. The minimum and maximum values for Current plished via the Autocycle feature. Load, GFEP and Temperatures are stored. Once the new high or low value is attained the old value is over- To enable the Auto Cycle feature, select an Auto Cycle written and displayed in the Autocycle tab text boxes. Interval greater than 0 hours within the System tab. See Figure 10. See Figure 9. The Auto Cycle feature is disabled when the Auto Cycle Interval equals 0 hours. Figure 10 This provides a certain level of preventative mainte- nance of the system as Faults (Alarms) will present themselves accordingly. Problem areas can be ad- dressed during non-essential operating periods. Autocycle Tab Navigation notes: Warning: 1. Each screen illustrates 6 loops at a time. To make It is NOT advisable to engage the Auto Cycle setting changes to loops beyond the current screen feature during normal operating periods. The within the Autocycle tab, one must select the Loop heating cables will become fully energized for Navigation buttons in the upper right or left of approximately 2 minutes throughout the Auto screen. Cycle Interval which could cause undesirable temperature overshoot. 16

20 Communications Remote Monitoring All changes to the MODBUS settings are achieved via & System Management the COMMS screen. See Figure 11. Users may monitor as well as adjust the System Pa- The Comms (Communications) screen may be ac- rameters settings of the panel remotely. The files re- cessed by selecting the COMMS button located at the quired for this feature are available to the owner. Due to bottom of any screen. The MODBUS Address, Baud the frequent program updates, we ask that you contact Rate, Parity and Stop parameters are set within the the factory for the most recent release version. Communications screen. For complete communications specification details on ModBus messaging, Registers and I/O Mapping, please reference our ModBus Message Set Specifi- cation For Heat Trace Control Panel Communication manual. Figure 11 17

21 Event Log The purpose of Event Log is to record every alarm new file is renamed to the current date, for example, condition with a date and time stamp. This log may 03292011104504.txt which is March 29th 2011, at be viewed via the LOGS button at the bottom of any 11:45:04 AM. This process repeats indefinitely which screen. See Figure 12. allows the owner to store as many files as needed with- out losing record of any of the alarms. Alarm condition example: Sensor Error alarm on chan- nel 18 will be recorded as 11/08/12 13:38:48 chan- To extract these files, one must: nel18 SENS_ERROR. Every alarm event is saved into 1. Plug a USB flash drive into the USB port located a text file (\Storage Card\log5.txt). Each event is ap- on the back of the ITLS/ITAS computer. Select My pended to the file string on a new line. computer, your USB drive will be visible as Hard This file holds up to 500 events (alarms). If the num- Disk folder. ber of entries exceeds 500 then the file is automatically 2. Enter \Storage Card\ folder and copy the log5. copied into an archive folder (\Storage Card\Archive) txt file (and Archive folder if needed) to your USB and the old log5.txt file is cleared. The name of the drive. Figure 12 18

22 Faults (Alarms) Clearing Alarms Faults within any 6-circuit or loop grouping are indicted Except for a Communications Alarm condition, all oth- by RED ovals in the left and right panels on any screen. er alarms are cleared once the acceptable parameters If the oval is GREEN, then no faults exist within that are achieved. However, the alarm(s) may be cleared by 6-circuit grouping. Once a fault is realized within any pressing the RESET ALM button found at the bottom 6-loop grouping, one may view the individual fault loop of any screen. This has no effect on the actual read- or loops in two different ways: ings. Therefore, unless the fault problem is resolved, the fault condition will return. 1. When in the Main Menu screen, one may navigate to the desired 6-loop grouping via the Navigation buttons found in the upper right hand or upper left hand corner. Fault conditions are illustrated within each loop window. Up to three alarm conditions can be illustrated for any single loop on the Main Menu screen. 2. One may view the status of all fault conditions by selecting the FAULTS button located at the bottom of any screen. To navigate to the desired 6-loop grouping, one must press the Loop Navigation but- tons found in the upper right or left corner of any screen. See Figure 13. Figure 13 19

23 Alarm Troubleshooting The Alarm Condition, the resultant Output and the Design Behavior for each Alarm type can be found in Table 2 below. Table 2 Alarm Type Condition Output Design Behavior HIGH TEMP Sensed Temp No change Alarm will be cleared automatically when > Hi Temp Sensed Temp < Hi Temp Setpoint Setpoint LOWTEMP Sensed Temp No change Alarm will be cleared automatically when < Lo Temp Sensed Temp > Lo Temp Setpoint Setpoint GFEP Sensed GFEP Trip Latch Current > No No Output will re- GFEP Setpoint main at selected output %. Alarm will be cleared automatically when Yes No Output will go to sensed GFEP Current < GFEP Setpoint 0% (OFF) while in alarm state No Yes Output will re- main at selected output %. The Alarm condition may only be cleared Yes Yes Output will go to with a manual RESET of the GFEP Alarm. 0% (OFF) until alarm is reset HI CURRENT Sensed Load Output will switch to Manual Alarm will be cleared automatically when (LOAD on Faults Current > Mode sensed Load Current < Hi Current Setpoint Screen) Hi Current Setpoint LO CURRENT Sensed Load No change Alarm will clear automatically when (LOAD on Faults Current < Lo Sensed Load Current > Lo Current Set- Screen) Current point. If your output is turned OFF, GFEP Setpoint and Load values will not be updated. SENSOR Sensor Open, Output will switch to Manual Alarm will clear automatically when the Sensor Shorted, Mode RTD resistance is between 75.44W - Sensor Fault 311.56W. Check if your sensor wire is not damaged and that it is properly connected to the Sensor board. COMM Communication Output will switch to Manual Make sure that the communication cable Error Mode that connects the Touchscreen computer with boards inside enclosure is properly connected and/or not broken. Press RESET ALM to reset this alarm. 20

24 Extension Panels Connection & Considerations Connecting the Extension panel to the Make sure that RX+ is connected to RX+ and Main Panel RX- to RX-. (See Diagram Below) Below is the procedure to connect an Extension Panel 4. Connect the metallic shielding material (see wire to the Main Panel. The Main Panel will control the cir- specification below) to the ground of the base panel cuits in the Extension Panel. Distribution Module. However, DO NOT connect the metallic shielding to the Extension Panel Distribu- Procedure: tion Module. (See Diagram Below) 1. Turn off the power to the system. 5. If the number of loops needs to be changed, power 2. In the main panel (the one with a touch screen com- up the system and login into the setup menu using puter) locate the distribution board (0113-10246) 5731 as the password. Go to the System tab and and verify that jumpers J.16 and J.17 are set in po- select the desired number of loops and press OK. sitions 1 & 2. 6. Cycle power to the system. 3. Connect one end of the twisted pair cable into con- nectors J15.1 (RX+) and J15.2 (RX-) on the distribu- tion board of the Main Panel. Connect the other end of the twisted pair cable into connector J15.1 RX+ and J15.2 (RX-) on the distribution board of the Ex- tension panel. Figure 14 Main Panel Extension Panel 2,500 FT (775 M) Max RX+ RX+ Main Panel Extension Panel Distribution RX- RX- Distribution Module GND GND Module Extension Panel Considerations Environmental influences such as EMI/RFI can com- Chromalox uses the following vendor and cable item promise the communication signal between the Ex- as a viable reference: tension Panel and the Main Panel. The use of properly Example Vendor:.................................................L-com designed cable will protect against and minimize these Typical Specification:....2 - 120 Ohm (E1) Shielded Pair influences. Vendor Item Number:..................................... TSC9928 Available at:............................... http://www.l-com.com Here is a design guide for extension panel wiring: RS-485 Maximum cable length.......... 2,500 FT (800 M) RS-485 Wire specification..........T1/E1/DSL compatible 24-AWG shielded cable 21

25 Service Contact information Chromalox is a global supplier, providing the highest level of customer support. If you should have questions concerning your intelliTRACE ITLS/ITAS control panel, or need information, you may contact Chromalox at: Corporate Headquarters Controls Division Chromalox Chromalox 103 Gamma Drive 1347 Heil-Quaker Blvd Pittsburgh, PA 15238 LaVergne, TN 37086 Phone: (412) 967-3800 Phone: (615) 793-3900 Customer Service Hotline: 1-800-443-2640 For application questions, you can: 1. Call one of our application engineers for personal assistance at 1-800-443-2640. 2. Visit the technical reference section of our website at www.chromalox.com for downloadable manuals in PDF format. 22

26 Appendix Panel Specifications Supply Voltage: ............................................ 100 - 480 VAC, 3 phase Operating Environment:................................ -40 to +104F (-40 to +40C) Enclosure....................................................... NEMA 4 or Optional NEMA 4X 304 SS Enclosure Size............................................... See Model Description Tables Communications:.......................................... RS-485 MODBUS, Ethernet & Optional Wireless Alarms:.......................................................... Hi/Lo Temp, GFEP 20 mA 150 mA, adjustable Current 0.1 to 50A or off, indication & annunciation Input: ............................................................ 100 Platinum 3-wire RTD Output: ......................................................... SCR, Zero cross fired Current Maximum:......................................... 40 Amps/Circuit at 104F (+40C) Auto-Cycle: ................................................... 1 999 hours/off Failed Sensor Output Setting:....................... 0 100% Control Mode: .............................................. Auto, Manual (Hand), Off Auto: PID or ON/OFF with adjustable dead band Manual: 0% - 100% output, 1% increment Load Management: ...................................... DOT (Demand On Transfer) timing, with Soft Start Approvals...................................................... UL, cUL, CE available Default Settings Below is the parameter settings chart organized by Menu Screen. It includes the default, minimum, maximum and/ or the range of settings, where applicable. Parameter Default Min Max Temperature Setpoint 0F (-17.7C) -80F (26.6C) 1100F (593.3C) Hi Temp Setpoint 200F (93.3C) -80F (26.6C) 1100F (593.3C) Lo Temp Setpoint 33F (0.5C) -80F (26.6C) 1100F (593.3C) HI Current 50 Amp 0.2 Amp 50 Amp Lo Current 0.2 Amp 0 Amp 50 Amp GFEP 30 mA 20 mA 150 mA Control Mode Manual Manual Auto Output % 0 0 100 Integral 8 0 100 Derivative 2 0 500 PID or ON/OFF On/OFF PID On/OFF Soft Start Enabled Enabled Disabled 23

27 Model Descriptions ITLS Line Sensing: 6 to 36 Loops, Non-Hazardous Environment ITLS ITLS Series Intelligent Line Sensing Heat Trace Panel. Designed for industrial applications in non-hazardous areas. ITLS series offers the following standard features: NEMA 4 enclosure, industrial 10 digital CE computer touchscreen operator interface, PID SCR power controller rated at 40A per circuit at 104F ambient, six to thirty-six circuits (expandable to seventy-two circuits*), common alarm output, hand/off/auto operation, 120 volt instrument power included, current monitoring, 30 mA ground fault equipment protection, RS485 ModBus/Ethernet communications, UL & cUL third party compliance. Options include: NEMA 4XSS Enclosure, remote monitoring capability, thermostat controlled enclosure heater, customizable I/O mapping, wireless ethernet communications, CE third party compliance. Code Circuits Enclosure Size (1 Input per Circuit) Panel Board Panel Board 1 Pole 2 Pole Size Main Bus Rating 06 6 Circuits 24H x 24W x 12D 24H x 24W x 12D N/A N/A 12 12 Circuits 36H x 30W x 12D ------- 18 Position up to 100A 12 12 Circuits 48H x 36W x 12D 48H x 36W x 12D 30 Position up to 400A 18 18 Circuits 48H x 36W x 12D ------- 30 position up to 400A 18 18 Circuits ------- 60H x 36W x 12D 42 position up to 600A 24 24 Circuits 48H x 36W x 12D ------- 30 position up to 400A 24 24 Circuits ------- 62H x 60W x 12D 30 position (X2) up to 400A 30 30 Circuits 60H x 36W x 12D ------- 30 position up to 600A 30 30 Circuits ------- 62H x 60W x 12D 42 position (X2) up to 600A 36 36 Circuits 60H x 36W x 12D ------- 42 position up to 600A 36 36 Circuits ------- 62H x 60W x 12D 42 position (X2) up to 600A Code Line Voltage Cable Voltage Circuit Breaker Rating - Type (1/Loop) 1 208/120 VAC, 3 Phase 4 Wire 120 VAC 120V 1-Pole 2 208/120 VAC, 3 Phase 4 Wire 208 VAC 208/240V 2-Pole 3 240/120 VAC, Single Phase 3 Wire 240 VAC 208/240V 2-Pole 4 480/277 VAC, 3 Phase 4 Wire 277 VAC 277V 1-Pole 5 480/277 VAC, 3 Phase 4 Wire 480 VAC 480V 2-Pole 6 240/120 VAC, Single Phase 3 Wire 120 VAC 120V 1-Pole Code Cable Load Circuit Breaker Rating 1 15A Thermal Magnetic 2 20A Thermal Magnetic 3 30A Thermal Magnetic 4 40A Thermal Magnetic 5 50A Thermal Magnetic Code Main Disconnects Code Main Circuit Breaker 0 -None A 100A Thermal Magnetic 1 - 100A Disconnect B 150A Thermal Magnetic 2 - 150A Disconnect C 225A Thermal Magnetic 3 - 250A Disconnect D 250A Thermal Magnetic 4 - 400A Disconnect E 400A Thermal Magnetic Code Enclosure Choose the Size that aligns with the Number of INPUTS PER CIRCUIT 1 NEMA 4 Single-Door Wall-Mount Steel Enclosure 2 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 24H x 24W x 12D 3 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 36H x 30W x 12D 4 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 48H x 36W x 12D 5 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 60H x 36W x 12D 6 NEMA 4X 304 Stainless Steel Floor-Mount Enclosure 62H x 60W x 12D Code Enclosure Heater 0 No Enclosure Heater 1 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater) 2 Thermostat Controlled Enclosure Heater (to 0F Ambient) 3 Thermostat Controlled Enclosure Heater (to -40F Ambient) Code Inputs / Circuit I/O Mapping 0 1 No I/O Mapping 1 1 Full I/O Mapping 2 2 Full I/O Mapping 3 3 Full I/O Mapping 9 X Special Configuration CodeCommunications 0 Standard: RS485 ModBus/RTU or Wired Eithernet 1 Wireless Ethernet 9 Other Consult Sales CodeMonitoring 0 Standard Monitoring (Local HMI Only) 1 Remote Desktop (Wired/Wireless Ethernet Only) 9 Other Consult Sales ITLS - 24 1 3 3 - 1 1 1 0 0 Typical Model Number *42 - 72 circuit service via ITLS-EXT Extension Panel. See ITLS-EXT heat Tracing Extension Panel - Line Sensing Order table. 24

28 Spare / Replacement Parts Model Number Note: Xxxx indicates that the design has varied from the order table Part parameters. This could include one or more of the following non- Number Item Description standard considerations: special software or configuration, private 0135-02261 SSR/GFI Power Control Assy., with Heat Sink branding, remote monitoring/touch-screen computer, sunshield or other protective covering, third party approval, floor stands, mount- 0135-02262 RTD Sensor Input Board Assembly ing options, special materials (316 SS) or coatings, additional vent- 0135-02263 Digital Distribution Comm Board Assembly ing or cooling, special indication or alarms. 0002-60054 SSR, 40 Amp rated 0029-00640 SSR Thermstrate Material Technical Notes 0025-05227 Common Alarm Relay 1. 120V instrument power included 2. Standard SCCR is 5 KA. Consult sales if different SCCR is needed. 0081-10063 Power Supply 5VDC 6A 30W DIN Rail Mount 3. Do Not Exceed 80% of Panelboard Rating 0081-10047 Power Supply 24VDC 2.5A 60W DIN Rail Mount 4. See ITLS-EXT Extension Panel Order Table to increase total circuits ITLS Digital Control 10 Display, Programmed Cable Load Circuit Breaker - Total Adder 0017-42931 15A 1P Thermal Mag Circuit Breaker (120V) 0017-43355 20A 1P Thermal Mag Circuit Breaker (120V) 120V 208/240V 277V 480V Circuits 1-Pole 2-Pole 1-Pole 2-Pole 0017-43356 30A 1P Thermal Mag Circuit Breaker (120V) 06 0017-43427 40A 1P Thermal Mag Circuit Breaker (120V) 0017-43428 50A 1P Thermal Mag Circuit Breaker (120V) 12 0017-43373 15A 2P Thermal Mag Circuit Breaker (208/240V) 18 0017-43374 20A 2P Thermal Mag Circuit Breaker (208/240V) 24 0017-43345 30A 2P Thermal Mag Circuit Breaker (208/240V) 30 0017-43375 40A 2P Thermal Mag Circuit Breaker (208/240V) 36 0017-43429 50A 2P Thermal Mag Circuit Breaker (208/240V) 0017-43013 15A 1P Thermal Mag Circuit Breaker (277V) ITLSC1D2 & ITLSC1D2-EXT I/O Mapping: 0017-42912 20A 1P Thermal Mag Circuit Breaker (277V) Enclosure Size & Total Adder 0017-42913 30A 1P Thermal Mag Circuit Breaker (277V) 0017-43349 40A 1P Thermal Mag Circuit Breaker (277V) Enclosure Size Adder 0017-42966 50A 1P Thermal Mag Circuit Breaker (277V) 2 Inputs per 3 Inputs per 0017-42970 15A 2P Thermal Mag Circuit Breaker (480V) Ckts - Output in In. Output in In. 3 Inputs 0017-43000 20A 2P Thermal Mag Circuit Breaker (480V) Poles (H x W x D) (H x W x D) Output per Output 06-1 24x24x12 36x30x12 0017-42928 30A 2P Thermal Mag Circuit Breaker (480V) 06-2 24x24x12 36x30x12 0017-43430 40A 2P Thermal Mag Circuit Breaker (480V) 12-1 36x30x12 48x36x12 0017-43431 50A 2P Thermal Mag Circuit Breaker (480V) 12-1 48x36x12 48x36x12 Accessories 12-2 48x36x12 48x36x12 18-1 48x36x12 48x36x12 Part 18-2 60x36x12 60x36x12 Number Item Description 24-1 48x36x12 48x36x12 Consult Factory Power Transformers 24-2 62x60x12 62x60x12 317315 RTD, Aluminum, NEMA 4, Pipe Mount 30-1 60x36x12 Consult Sales Consult Sales 317340 RTD, Expl. Resist., NEMA 4, Pipe Mount 30-2 62x60x12 Consult Sales Consult Sales 308056 RTD, Snap Lid, Alum, Ambient Sensing 36-1 60x36x12 Consult Sales Consult Sales 308144 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 50 FT 36-2 62x60x12 Consult Sales Consult Sales 317342 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 200 FT 0076-12009 Floor Stand Kit, 12 Deep, Steel I/O Mapping Notes 1. The MAXIMUM number of Inputs for any ITLS System, including 0076-12050 Floor Stand Kit, 12 Deep, 304 SS Extension Panel, is 72. 2. When Full I/O Mapping is selected from the Order Table, any in- Consult Factory Floor Stand Kit, 12 Deep, 316 SS dividual sensor or output may be mapped to moren than one circuit. For Example: The average temperature of Sensors 1, 2 & CE Third Party Compliance 3 is used to control Circuit 1 while simultaneously the maximum temperature of Sensors 3, 4 & 5 is used to control Circuit 2. Base Panel Model Number Instructions Maximum Number of Available Inputs per Panel Design ITLS-06 Add -CEXX suffix to Model Number Inputs / Circuit Code from Order Tables ITLS-12 Add -CEXX suffix to Model Number Circuits 1 2 3 ITLS-18 Add -CEXX suffix to Model Number 06 06 12 18 ITLS-24 Add -CEXX suffix to Model Number 12 12 24 36 ITLS-30 Add -CEXX suffix to Model Number 18 18 36 54 ITLS-36 Add -CEXX suffix to Model Number 24 24 48 72 30 30 60 Consult Sales 36 36 72 Consult Sales 25

29 ITLS-EXT Extender Panel for the ITLS (Add up to 36 additional loops) ITLS-EXT ITLS-EXT Series Intelligent Line Sensing Heat Trace Extension Panel. Designed for industrial applications in non-hazardous areas. Intended to be used with ITLS heat trace line sensing panel to increase circuit service. ITLS-EXT series offers the following standard features: NEMA 4 enclosure, PID SCR power controller rated at 40A per circuit at 104F ambient, six to thirty-six circuits, common alarm output, hand/off/auto operation, current monitoring, 30 mA ground fault equip- ment protection, RS 485 ModBus ethernet communications, UL & cUL third party compliance. Options include: NEMA 4XSS enclosure, thermostat controlled enclosure heater, customizable I/O mapping, remote monitoring capability, CE third party compliance Code Circuits Enclosure Size (1 Input per Circuit) Panel Board Panel Board 1 Pole 2 Pole Size Main Bus Rating 06 6 Circuits 24H x 24W x 12D 24H x 24W x 12D N/A N/A 12 12 Circuits 36H x 30W x 12D ------- 18 Position up to 100A 12 12 Circuits 48H x 36W x 12D 48H x 36W x 12D 30 Position up to 400A 18 18 Circuits 48H x 36W x 12D ------- 30 position up to 400A 18 18 Circuits ------- 60H x 36W x 12D 42 position up to 600A 24 24 Circuits 48H x 36W x 12D ------- 30 position up to 400A 24 24 Circuits ------- 62H x 60W x 12D 30 position (X2) up to 400A 30 30 Circuits 60H x 36W x 12D ------- 30 position up to 600A 30 30 Circuits ------- 62H x 60W x 12D 42 position (X2) up to 600A 36 36 Circuits 60H x 36W x 12D ------- 42 position up to 600A 36 36 Circuits ------- 62H x 60W x 12D 42 position (X2) up to 600A Code Line Voltage Cable Voltage Circuit Breaker Rating - Type (1/Loop) 1 208/120 VAC, 3 Phase 4 Wire 120 VAC 120V 1-Pole 2 208/120 VAC, 3 Phase 4 Wire 208 VAC 208/240V 2-Pole 3 240/120 VAC, Single Phase 3 Wire 240 VAC 208/240V 2-Pole 4 480/277 VAC, 3 Phase 4 Wire 277 VAC 277V 1-Pole 5 480/277 VAC, 3 Phase 4 Wire 480 VAC 480V 2-Pole 6 240/120 VAC, Single Phase 3 Wire 120 VAC 120V 1-Pole Code Cable Load Circuit Breaker Rating 1 15A Thermal Magnetic 2 20A Thermal Magnetic 3 30A Thermal Magnetic 4 40A Thermal Magnetic 5 50A Thermal Magnetic Code Main Disconnects Code Main Circuit Breaker 0 -None A 100A Thermal Magnetic 1 - 100A Disconnect B 150A Thermal Magnetic 2 - 150A Disconnect C 225A Thermal Magnetic 3 - 250A Disconnect D 250A Thermal Magnetic 4 - 400A Disconnect E 400A Thermal Magnetic 5 - 600A Disconnect F 600A Thermal Magnetic Code Enclosure Choose the size that aligns with the Number of INPUTS PER CIRCUIT 1 NEMA 4 Single-Door Wall-Mount Steel Enclosure 2 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 24H x 24W x 12D 3 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 36H x 30W x 12D 4 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 48H x 36W x 12D 5 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 60H x 36W x 12D 6 NEMA 4X 304 Stainless Steel Floor-Mount Enclosure 62H x 60W x 12D Code Enclosure Heater 0 No Enclosure Heater 1 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater) 2 Thermostat Controlled Enclosure Heater (to 0F Ambient) 3 Thermostat Controlled Enclosure Heater (to -40F Ambient) Code Inputs / Circuit I/O Mapping 0 1 No I/O Mapping 1 1 Full I/O Mapping 2 2 Full I/O Mapping 3 3 Full I/O Mapping 9 X Special Configuration ITLS - EXT- 24 1 3 3 - 1 1 1 Typical Model Number * Designed to be paired w ith an ITLS Panel ** This code must match the same code on the Base ITLS Panel Technical Notes - ITLS, ITLS-EXT 1. 120V instrument power included 2. Our standard SCCR is 5 KA. Consult sales if a different SCCR is needed. 3. Do Not Exceed 80% of Panelboard Rating 4. See ITLS-EXT Extension Panel Order Table to increase total circuits 26

30 Spare / Replacement Parts Model Number Note: Xxxx indicates that the design has varied from the order table Part parameters. This could include one or more of the following non- Number Item Description standard considerations: special software or configuration, private 0135-02261 SSR/GFI Power Control Assy., with Heat Sink branding, remote monitoring/touch-screen computer, sunshield or other protective covering, third party approval, floor stands, mount- 0135-02262 RTD Sensor Input Board Assembly ing options, special materials (316 SS) or coatings, additional vent- 0135-02263 Digital Distribution Comm Board Assembly ing or cooling, special indication or alarms. 0002-60054 SSR, 40 Amp rated 0029-00640 SSR Thermstrate Material Technical Notes 0025-05227 Common Alarm Relay 1. 120V instrument power included 2. Standard SCCR is 5 KA. Consult sales if different SCCR is needed. 0081-10063 Power Supply 5VDC 6A 30W DIN Rail Mount 3. Do Not Exceed 80% of Panelboard Rating 0081-10047 Power Supply 24VDC 2.5A 60W DIN Rail Mount 4. See ITLS-EXT Extension Panel Order Table to increase total circuits 0017-42931 15A 1P Thermal Mag Circuit Breaker (120V) Cable Load Circuit Breaker - Total Adder 0017-43355 20A 1P Thermal Mag Circuit Breaker (120V) 0017-43356 30A 1P Thermal Mag Circuit Breaker (120V) 120V 208/240V 277V 480V 0017-43427 40A 1P Thermal Mag Circuit Breaker (120V) Circuits 1-Pole 2-Pole 1-Pole 2-Pole 06 0017-43428 50A 1P Thermal Mag Circuit Breaker (120V) 0017-43373 15A 2P Thermal Mag Circuit Breaker (208/240V) 12 0017-43374 20A 2P Thermal Mag Circuit Breaker (208/240V) 18 0017-43345 30A 2P Thermal Mag Circuit Breaker (208/240V) 24 0017-43375 40A 2P Thermal Mag Circuit Breaker (208/240V) 30 0017-43429 50A 2P Thermal Mag Circuit Breaker (208/240V) 36 0017-43013 15A 1P Thermal Mag Circuit Breaker (277V) 0017-42912 20A 1P Thermal Mag Circuit Breaker (277V) ITLSC1D2 & ITLSC1D2-EXT I/O Mapping: 0017-42913 30A 1P Thermal Mag Circuit Breaker (277V) Enclosure Size & Total Adder 0017-43349 40A 1P Thermal Mag Circuit Breaker (277V) 0017-42966 50A 1P Thermal Mag Circuit Breaker (277V) Enclosure Size Adder 0017-42970 15A 2P Thermal Mag Circuit Breaker (480V) 2 Inputs per 3 Inputs per 0017-43000 20A 2P Thermal Mag Circuit Breaker (480V) Ckts - Output in In. Output in In. 3 Inputs 0017-42928 30A 2P Thermal Mag Circuit Breaker (480V) Poles (H x W x D) (H x W x D) Output per Output 0017-43430 40A 2P Thermal Mag Circuit Breaker (480V) 06-1 24x24x12 36x30x12 0017-43431 50A 2P Thermal Mag Circuit Breaker (480V) 06-2 24x24x12 36x30x12 12-1 36x30x12 48x36x12 12-1 48x36x12 48x36x12 12-2 48x36x12 48x36x12 Accessories 18-1 48x36x12 48x36x12 Part 18-2 60x36x12 60x36x12 Number Item Description 24-1 48x36x12 48x36x12 Consult Factory Power Transformers 24-2 62x60x12 62x60x12 317315 RTD, Aluminum, NEMA 4, Pipe Mount 30-1 60x36x12 Consult Sales Consult Sales 30-2 62x60x12 Consult Sales Consult Sales 317340 RTD, Expl. Resist., NEMA 4, Pipe Mount 36-1 60x36x12 Consult Sales Consult Sales 308056 RTD, Snap Lid, Alum, Ambient Sensing 36-2 62x60x12 Consult Sales Consult Sales 308144 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 50 FT 317342 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 200 FT 0076-12009 Floor Stand Kit, 12 Deep, Steel I/O Mapping Notes 1. The MAXIMUM number of Inputs for any ITLS System, including 0076-12050 Floor Stand Kit, 12 Deep, 304 SS Extension Panel, is 72. 2. When Full I/O Mapping is selected from the Order Table, any in- Consult Factory Floor Stand Kit, 12 Deep, 316 SS dividual sensor or output may be mapped to moren than one circuit. For Example: The average temperature of Sensors 1, 2 & CE Third Party Compliance 3 is used to control Circuit 1 while simultaneously the maximum temperature of Sensors 3, 4 & 5 is used to control Circuit 2. Base Panel Model Number Instructions Maximum Number of Available Inputs per Panel Design ITLS-06 Add -CEXX suffix to Model Number Inputs / Circuit Code from Order Tables ITLS-12 Add -CEXX suffix to Model Number Circuits 1 2 3 ITLS-18 Add -CEXX suffix to Model Number 06 06 12 18 ITLS-24 Add -CEXX suffix to Model Number 12 12 24 36 ITLS-30 Add -CEXX suffix to Model Number 18 18 36 54 ITLS-36 Add -CEXX suffix to Model Number 24 24 48 72 30 30 60 Consult Sales 36 36 72 Consult Sales 27

31 ITAS Ambient Sensing: 6 to 36 Loops, Non-Hazardous Environment ITAS ITAS Series Intelligent Ambient Sensing Heat Trace Panel. Designed for industrial applications in non-hazardous areas. ITAS series offers the following standard features: NEMA 4 enclosure, industrial 10 digital CE computer touchscreen operator interface, PID SCR power controller rated at 40A per circuit at 104F ambient, six to thirty-six circuits (expandable to seventy-two circuits*), common alarm output, hand/off/auto operation, current monitoring, 30 mA ground fault equipment protection, RS485 ModBus / Ethernet communications, UL & cUL third party compliance. Options Include: NEMA 4XSS enclosure, thermostat controlled enclosure heater, remote monitoring capability, wireless ethernet communications, CE third party compliance Code Circuits Enclosure Size (1 Input per Circuit) Panel Board Panel Board 1 Pole 2 Pole Size Main Bus Rating 06 6 Circuits 24H x 24W x 12D 24H x 24W x 12D N/A N/A 12 12 Circuits 36H x 30W x 12D ------- 18 Position up to 100A 12 12 Circuits 48H x 36W x 12D 48H x 36W x 12D 30 Position up to 400A 18 18 Circuits 48H x 36W x 12D ------- 30 position up to 400A 18 18 Circuits ------- 60H x 36W x 12D 42 position up to 600A 24 24 Circuits 48H x 36W x 12D ------- 30 position up to 400A 24 24 Circuits ------- 62H x 60W x 12D 30 position (X2) up to 400A 30 30 Circuits 60H x 36W x 12D ------- 30 position up to 600A 30 30 Circuits ------- 62H x 60W x 12D 42 position (X2) up to 600A 36 36 Circuits 60H x 36W x 12D ------- 42 position up to 600A 36 36 Circuits ------- 62H x 60W x 12D 42 position (X2) up to 600A Code Line Voltage Cable Voltage Circuit Breaker Rating - Type (1/Loop) 1 208/120 VAC, 3 Phase 4 Wire 120 VAC 120V 1-Pole 2 208/120 VAC, 3 Phase 4 Wire 208 VAC 208/240V 2-Pole 3 240/120 VAC, Single Phase 3 Wire 240 VAC 208/240V 2-Pole 4 480/277 VAC, 3 Phase 4 Wire 277 VAC 277V 1-Pole 5 480/277 VAC, 3 Phase 4 Wire 480 VAC 480V 2-Pole 6 240/120 VAC, Single Phase 3 Wire 120 VAC 120V 1-Pole Code Cable Load Circuit Breaker Rating 1 15A Thermal Magnetic 2 20A Thermal Magnetic 3 30A Thermal Magnetic 4 40A Thermal Magnetic 5 50A Thermal Magnetic Code Main Disconnects Code Main Circuit Breaker 0 -None A 100A Thermal Magnetic 1 - 100A Disconnect B 150A Thermal Magnetic 2 - 150A Disconnect C 225A Thermal Magnetic 3 - 250A Disconnect D 250A Thermal Magnetic 4 - 400A Disconnect E 400A Thermal Magnetic 5 - 600A Disconnect F 600A Thermal Magnetic CodeEnclosure 1 NEMA 4 Single-Door Wall-Mount Steel Enclosure 2 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 24H x 24W x 12D 3 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 36H x 30W x 12D 4 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 48H x 36W x 12D 5 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 60H x 36W x 12D 6 NEMA 4X 304 Stainless Steel Floor-Mount Enclosure 62H x 60W x 12D Code Enclosure Heater 0 No Enclosure Heater 1 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater) 2 Thermostat Controlled Enclosure Heater (to 0F Ambient) 3 Thermostat Controlled Enclosure Heater (to -40F Ambient) Code Sensor Options & Sensor Mapping 0 No Sensor Mapping 9 Special Configuration CodeCommunications 0 Standard: RS485 ModBus/RTU or Wired Eithernet 1 Wireless Ethernet 9 Other CodeMonitoring 0 Standard Monitoring (Local HMI Only) 1 Remote Desktop (Wired/Wireless Ethernet Only) 9 Other ITAS - 24 1 3 3 - 1 1 1 0 0 Typical Model Number *42 - 72 circuit service via ITAS-EXT Extension Panel. See ITAS-EXT Heat Tracing Extension Panel - Ambient Sensing Order table. Technical Notes 1. 120-264V customer supplied instrument power supply 2. Do Not Exceed 80% of Panelboard Rating 3. See ITAS-EXT Extension Panel Order Table to increase total circuits 28

32 Spare / Replacement Parts CE Third Party Compliance Part Number Item Description Base Panel Model Number Instructions ITAS-06 Add -CEXX suffix to Model Number 0135-02261 SSR/GFI Power Control Assy., with Heat Sink 0135-02262 RTD Sensor Input Board Assembly ITAS-12 Add -CEXX suffix to Model Number 0135-02263 Digital Distribution Comm Board Assembly ITAS-18 Add -CEXX suffix to Model Number 0002-60054 SSR, 40 Amp rated ITAS-24 Add -CEXX suffix to Model Number 0029-00640 SSR Thermstrate Material ITAS-30 Add -CEXX suffix to Model Number 0025-05227 Common Alarm Relay ITAS-36 Add -CEXX suffix to Model Number 0081-10063 Power Supply 5VDC 6A 30W DIN Rail Mount 0081-10047 Power Supply 24VDC 2.5A 60W DIN Rail Mount Model Number Note: 0135-30490 ITAS Digital Control 10 Display, Programmed Xxxx indicates that the design has varied from the order table 0017-42931 15A 1P Thermal Mag Circuit Breaker (120V) parameters. This could include one or more of the following non- standard considerations: special software or configuration, private 0017-43355 20A 1P Thermal Mag Circuit Breaker (120V) branding, remote monitoring/touch-screen computer, sunshield or 0017-43356 30A 1P Thermal Mag Circuit Breaker (120V) other protective covering, third party approval, floor stands, mount- 0017-43427 40A 1P Thermal Mag Circuit Breaker (120V) ing options, special materials (316 SS) or coatings, additional vent- 0017-43428 50A 1P Thermal Mag Circuit Breaker (120V) ing or cooling, special indication or alarms. 0017-43373 15A 2P Thermal Mag Circuit Breaker (208/240V) 0017-43374 20A 2P Thermal Mag Circuit Breaker (208/240V) Technical Notes 1. 120V instrument power included 0017-43345 30A 2P Thermal Mag Circuit Breaker (208/240V) 2. Standard SCCR is 5 KA. Consult sales if different SCCR is needed. 0017-43375 40A 2P Thermal Mag Circuit Breaker (208/240V) 3. Do Not Exceed 80% of Panelboard Rating 0017-43429 50A 2P Thermal Mag Circuit Breaker (208/240V) 4. See ITLS-EXT Extension Panel Order Table to increase total circuits 0017-43013 15A 1P Thermal Mag Circuit Breaker (277V) 0017-42912 20A 1P Thermal Mag Circuit Breaker (277V) Cable Load Circuit Breaker - Total Adder 0017-42913 30A 1P Thermal Mag Circuit Breaker (277V) 120V 208/240V 277V 480V 0017-43349 40A 1P Thermal Mag Circuit Breaker (277V) Circuits 1-Pole 2-Pole 1-Pole 2-Pole 0017-42966 50A 1P Thermal Mag Circuit Breaker (277V) 06 0017-42970 15A 2P Thermal Mag Circuit Breaker (480V) 12 0017-43000 20A 2P Thermal Mag Circuit Breaker (480V) 18 0017-42928 30A 2P Thermal Mag Circuit Breaker (480V) 24 0017-43430 40A 2P Thermal Mag Circuit Breaker (480V) 30 0017-43431 50A 2P Thermal Mag Circuit Breaker (480V) 36 Accessories Part Number Item Description Consult Factory Power Transformers 317315 RTD, Aluminum, NEMA 4, Pipe Mount 317340 RTD, Expl. Resist., NEMA 4, Pipe Mount 308056 RTD, Snap Lid, Alum, Ambient Sensing 308144 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 50 FT 317342 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 200 FT 0076-12009 Floor Stand Kit, 12 Deep, Steel 0076-12050 Floor Stand Kit, 12 Deep, 304 SS Consult Factory Floor Stand Kit, 12 Deep, 316 SS 29

33 ITAS-EXT Extender Panel for the ITAS (Add up to 36 additional loops) ITAS-EXT ITAS-EXT Series Intelligent Ambient Sensing Heat Trace Extension Panel. Designed for industrial applications in non-hazardous areas. Intended to be used With ITAS Heat Trace Ambient Sensing Panel to increase circuit service. ITAS series offers the following standard features: NEMA 4 enclosure, PID SCR power controller rated at 40A per circuit at 104F ambient, six to thirty-six circuits, common alarm output, hand/off/auto operation, current monitoring, 30 mA cround fault equipment protection, RS 485 ModBus ethernet communications, UL & cUL third party compliance. Options include: NEMA 4XSS enclosure, remote monitoring capability, thermostat controlled enclosure heater, CE third party compliance Code Circuits Enclosure Size (1 Input per Circuit) Panel Board Panel Board 1 Pole 2 Pole Size Main Bus Rating 06 6 Circuits 24H x 24W x 12D 24H x 24W x 12D N/A N/A 12 12 Circuits 36H x 30W x 12D ------- 18 Position up to 100A 12 12 Circuits 48H x 36W x 12D 48H x 36W x 12D 30 Position up to 400A 18 18 Circuits 48H x 36W x 12D ------- 30 position up to 400A 18 18 Circuits ------- 60H x 36W x 12D 42 position up to 600A 24 24 Circuits 48H x 36W x 12D ------- 30 position up to 400A 24 24 Circuits ------- 62H x 60W x 12D 30 position (X2) up to 400A 30 30 Circuits 60H x 36W x 12D ------- 30 position up to 600A 30 30 Circuits ------- 62H x 60W x 12D 42 position (X2) up to 600A 36 36 Circuits 60H x 36W x 12D ------- 42 position up to 600A 36 36 Circuits ------- 62H x 60W x 12D 42 position (X2) up to 600A Code Line Voltage Cable Voltage Circuit Breaker Rating - Type (1/Loop) 1 208/120 VAC, 3 Phase 4 Wire 120 VAC 120V 1-Pole 2 208/120 VAC, 3 Phase 4 Wire 208 VAC 208/240V 2-Pole 3 240/120 VAC, Single Phase 3 Wire 240 VAC 208/240V 2-Pole 4 480/277 VAC, 3 Phase 4 Wire 277 VAC 277V 1-Pole 5 480/277 VAC, 3 Phase 4 Wire 480 VAC 480V 2-Pole 6 240/120 VAC, Single Phase 3 Wire 120 VAC 120V 1-Pole Code Cable Load Circuit Breaker Rating 1 15A Thermal Magnetic 2 20A Thermal Magnetic 3 30A Thermal Magnetic 4 40A Thermal Magnetic 5 50A Thermal Magnetic Code Main Disconnects Code Main Circuit Breaker 0 -None A 100A Thermal Magnetic 1 - 100A Disconnect B 150A Thermal Magnetic 2 - 150A Disconnect C 225A Thermal Magnetic 3 - 250A Disconnect D 250A Thermal Magnetic 4 - 400A Disconnect E 400A Thermal Magnetic 5 - 600A Disconnect F 600A Thermal Magnetic CodeEnclosure 1 NEMA 4 Single-Door Wall-Mount Steel Enclosure 2 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 24H x 24W x 12D 3 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 36H x 30W x 12D 4 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 48H x 36W x 12D 5 NEMA 4X 304 Stainless Steel Wall-Mount Enclosure 60H x 36W x 12D 6 NEMA 4X 304 Stainless Steel Floor-Mount Enclosure 62H x 60W x 12D Code Enclosure Heater 0 No Enclosure Heater 1 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater) 2 Thermostat Controlled Enclosure Heater (to 0F Ambient) 3 Thermostat Controlled Enclosure Heater (to -40F Ambient) ITAS - EXT- 24 1 3 1 - 1 0 Typical Model Number * Designed to be paired with an ITLS Panel Technical Notes 1. 120-264V customer supplied instrument power supply 2. Do Not Exceed 80% of Panelboard Rating 3. These Extension Panels are to be paired with an ITAS Panel. 30

34 Spare / Replacement Parts CE Third Party Compliance Part Base Panel Model Number Instructions Number Item Description ITAS-06 Add -CEXX suffix to Model Number 0135-02261 SSR/GFI Power Control Assy., with Heat Sink 0135-02262 RTD Sensor Input Board Assembly ITAS-12 Add -CEXX suffix to Model Number 0135-02263 Digital Distribution Comm Board Assembly ITAS-18 Add -CEXX suffix to Model Number 0002-60054 SSR, 40 Amp rated ITAS-24 Add -CEXX suffix to Model Number 0029-00640 SSR Thermstrate Material ITAS-30 Add -CEXX suffix to Model Number 0025-05227 Common Alarm Relay ITAS-36 Add -CEXX suffix to Model Number 0081-10063 Power Supply 5VDC 6A 30W DIN Rail Mount 0081-10047 Power Supply 24VDC 2.5A 60W DIN Rail Mount Model Number Note: 0017-42931 15A 1P Thermal Mag Circuit Breaker (120V) Xxxx indicates that the design has varied from the order table 0017-43355 20A 1P Thermal Mag Circuit Breaker (120V) parameters. This could include one or more of the following non- standard considerations: special software or configuration, private 0017-43356 30A 1P Thermal Mag Circuit Breaker (120V) branding, remote monitoring/touch-screen computer, sunshield or 0017-43427 40A 1P Thermal Mag Circuit Breaker (120V) other protective covering, third party approval, floor stands, mount- 0017-43428 50A 1P Thermal Mag Circuit Breaker (120V) ing options, special materials (316 SS) or coatings, additional vent- 0017-43373 15A 2P Thermal Mag Circuit Breaker (208/240V) ing or cooling, special indication or alarms. 0017-43374 20A 2P Thermal Mag Circuit Breaker (208/240V) Technical Notes 0017-43345 30A 2P Thermal Mag Circuit Breaker (208/240V) 1. 120-264V customer supplied instrument power supply 0017-43375 40A 2P Thermal Mag Circuit Breaker (208/240V) 2. Do Not Exceed 80% of Panelboard Rating 0017-43429 50A 2P Thermal Mag Circuit Breaker (208/240V) 3. These extension panels are to be paired with an ITAS panel. 0017-43013 15A 1P Thermal Mag Circuit Breaker (277V) 0017-42912 20A 1P Thermal Mag Circuit Breaker (277V) Cable Load Circuit Breaker - Total Adderp 0017-42913 30A 1P Thermal Mag Circuit Breaker (277V) 120V 208/240V 277V 480V 0017-43349 40A 1P Thermal Mag Circuit Breaker (277V) Circuits 1-Pole 2-Pole 1-Pole 2-Pole 0017-42966 50A 1P Thermal Mag Circuit Breaker (277V) 06 0017-42970 15A 2P Thermal Mag Circuit Breaker (480V) 12 0017-43000 20A 2P Thermal Mag Circuit Breaker (480V) 18 0017-42928 30A 2P Thermal Mag Circuit Breaker (480V) 24 0017-43430 40A 2P Thermal Mag Circuit Breaker (480V) 30 0017-43431 50A 2P Thermal Mag Circuit Breaker (480V) 36 Accessories Part Number Item Description Consult Factory Power Transformers 317315 RTD, Aluminum, NEMA 4, Pipe Mount 317340 RTD, Expl. Resist., NEMA 4, Pipe Mount 308056 RTD, Snap Lid, Alum, Ambient Sensing 308144 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 50 FT 317342 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 200 FT 0076-12009 Floor Stand Kit, 12 Deep, Steel 0076-12050 Floor Stand Kit, 12 Deep, 304 SS Consult Factory Floor Stand Kit, 12 Deep, 316 SS 31

35 ITLSC1D2 Line Sensing, Class I, Division 2 6 36 Loops, Hazardous Environment (Class I, Div 2) ITLSC1D2 ITLSC1D2 Series Intelligent Line Sensing Heat Trace Panel. Designed for industrial applications and suitable for Class I, Division 2 hazardous areas. The ITLSC1D2 series offers the following standard features: NEMA 4 enclosure, industrial 12 (30cm) digital CE computer touchscreen operator interface, PID SCR power controller rated at 40A per circuit at 104F (40C) ambient, six to thirty-six circuits (Expandable to Seventy-Two Circuits*), common alarm output, hand/ Off/auto operation, current monitoring, 30 mA ground fault equipment protection, RS485 ModBus / Ethernet communications, remote monitoring capability, selectable Soft Start operation, UL & cUL third party compliance. Options Include: NEMA 4XSS enclosure, customized I/O (Sensor & Output) mapping, wireless ethernet communications and CE certification Code Circuits Enclosure Size Line Voltage Line Phase Cable Voltage 06 6 Circuits 24H x 24W x 12D 120/208/240/277/480 1 120/208/240/277/480 12 12 Circuits 24H x 24W x 12D 120/208/240/277/480 1 120/208/240/277/480 18 18 Circuits 42H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 24 24 Circuits 42H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 30 30 Circuits 60H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 36 36 Circuits 60H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 Code Enclosure Rating Material Size Enclosure Mounting 1 NEMA 4 Painted Steel Size is per design selection Wall-Mount Enclosure 2 NEMA 4X 304 SS 24 x 24 x 12 Wall-Mount Enclosure 3 NEMA 4X 304 SS 42 x 36 x 12 Wall-Mount Enclosure 4 NEMA 4X 304 SS 48 x 36 x 12 Wall-Mount Enclosure 5 NEMA 4X 304 SS 60 x 36 x 12 Wall-Mount Enclosure Code Enclosure Heater Class 1, Div 2 0 No Enclosure Heater 1 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater) For use with 6 & 12 circuit designs 2 Thermostat Controlled Enclosure Heater (to 0F Ambient) For use with 6 & 12 circuit designs 3 Thermostat Controlled Enclosure Heater (to -40F Ambient) For use with 6 & 12 circuit designs 4 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater For use with 18, 24, 30 & 36 circuit designs 5 Thermostat Controlled Enclosure Heater (to 0F Ambient) For use with 18, 24, 30 & 36 circuit designs 6 Thermostat Controlled Enclosure Heater (to -40F Ambient) For use with 18, 24, 30 & 36 circuit designs Code Inputs/Circuit I/O Mapping 0 1 No I/O Mapping 1 1 Full I/O Mapping 2 2 Full I/O Mapping 3 3 Full I/O Mapping 9 X Special Configuration CodeCommunications 0 Standard: RS485 ModBus/RTU or Wired Eithernet 9 Other Consult Sales CodeMonitoring 0 Standard Monitoring (Local HMI Only) 1 Remote Desktop (Wired/Wireless Ethernet Only) 9 Other Consult Sales ITLSC1D2 - 24 1 4 3 - 0 0Typical Model Number *42 - 72 circuit service via ITLS-EXT Extension Panel. See ITLS-EXT Heat Tracing Extension Panel - Line Sensing Order table. Technical Notes 1. 120-264V customer supplied instrument power supply 2. Our standard SCCR is 5 KA. Consult sales if a different SCCR is needed. 3. Do Not Exceed 80% of Panelboard Rating 4. See ITLSC1D2-EXT Extension Panel Order Table to increase total circuits 32

36 Spare / Replacement Parts Model Number Note: Xxxx indicates that the design has varied from the order table Part parameters. This could include one or more of the following non- Number Item Description standard considerations: special software or configuration, private 0135-02261 SSR/GFI Power Control Assy., with Heat Sink branding, remote monitoring/touch-screen computer, sunshield or other protective covering, third party approval, floor stands, mount- 0135-02262 RTD Sensor Input Board Assembly ing options, special materials (316 SS) or coatings, additional vent- 0135-02263 Digital Distribution Comm Board Assembly ing or cooling, special indication or alarms. 0002-60054 SSR, 40 Amp rated 0029-00640 SSR Thermstrate Material Technical Notes 0025-05227 Common Alarm Relay 1. 120-264V customer supplied instrument power supply 2. Standard SCCR is 5 KA. Consult sales if different SCCR is needed. 0081-10063 Power Supply 5VDC 6A 30W DIN Rail Mount 3. Do Not Exceed 80% of Panelboard Rating 0081-10047 Power Supply 24VDC 2.5A 60W DIN Rail Mount 4. See ITLSC1D2-EXT Extension Panel Order Table to increase total ITLSC1D2 HMI 12 Diagonal, Programmed circuits ITLSC1D2 & ITLSC1D2-EXT I/O Mapping: Accessories Enclosure Size Part Enclosure Size H x W x D, In. (cm) Number Item Description 2 Inputs per 3 Inputs per Consult Factory Power Transformers Circuits Output Output 317315 RTD, Aluminum, NEMA 4, Pipe Mount 06 24x24x12 (61x61x31) 24x24x12 (61x61x31) 317340 RTD, Expl. Resist., NEMA 4, Pipe Mount 12 24x24x12 (61x61x31) 24x24x12 (61x61x31) 308056 RTD, Snap Lid, Alum, Ambient Sensing 308144 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 50 FT 18 42x36x12 (107x92x31) 42x36x12 (107x92x31) 317342 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 200 FT 24 42x36x12 (107x92x31) 48x36x12 (122x92x31) 0076-12009 Floor Stand Kit, 12 Deep, Steel 30 60x36x12 (152x92x31) Consult Sales 0076-12050 Floor Stand Kit, 12 Deep, 304 SS 36 60x36x12 (152x92x31) Consult Sales Consult Factory Floor Stand Kit, 12 Deep, 316 SS Total Number of Available Inputs per Panel Design Inputs / Circuit Code from Order Tables CE Third Party Compliance Circuits 1 2 3 Base Panel Model Number Instructions 06 06 12 18 ITLSC1D2-06 Add -CEXX suffix to Model Number 12 12 24 36 ITLSC1D2-12 Add -CEXX suffix to Model Number 18 18 36 54 ITLSC1D2-18 Add -CEXX suffix to Model Number 24 24 48 72 ITLSC1D2-24 Add -CEXX suffix to Model Number 30 30 60 Consult Sales ITLSC1D2-30 Add -CEXX suffix to Model Number 36 36 72 Consult Sales ITLSC1D2-36 Add -CEXX suffix to Model Number I/O Mapping Notes 1. The MAXIMUM number of Inputs for any ITLSC1D2 System, in- cluding Extension Panel, is 72. 2. When Full I/O Mapping is selected from the Order Table, any in- dividual sensor or output may be mapped to moren than one circuit. For Example: The average temperature of Sensors 1, 2 & 3 is used to control Circuit 1 while simultaneously the maximum temperature of Sensors 3, 4 & 5 is used to control Circuit 2. 33

37 ITLSC1D2-EXT Extender Panel for the ITLSC1D2, Class I, Div 2 (Add up to 36 additional Loops of Service) ITLSC1D2-EXT ITLSC1D2-EXT Series Intelligent Line Sensing Heat Trace Extension Panel. Designed for industrial applications and suitable for Class I, Division 2 Haz- ardous areas. Designed to be used with ITLSC1D2 heat trace line sensing panel to increase circuit service. ITLSC1D2-EXT series offers the following standard features: NEMA 4 enclosure, PID SCR power controller rated at 40A per circuit at 104F (40C) ambient, six to thirty-six circuits, common alarm output, Hand/Off/Auto operation, current monitoring, 30 mA ground fault equipment protection, RS 485 ModBus ethernet communications, UL & cUL third party compliance. Options include: NEMA 4XSS enclosure, thermostat controlled enclosure heater, customized I/O (Sensor & Output) mapping, remote monitoring capability, CE certification Code Circuits Enclosure Size Line Voltage Line Phase Cable Voltage 06 6 Circuits 24H x 24W x 12D 120/208/240/277/480 1 120/208/240/277/480 12 12 Circuits 24H x 24W x 12D 120/208/240/277/480 1 120/208/240/277/480 18 18 Circuits 42H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 24 24 Circuits 42H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 30 30 Circuits 60H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 36 36 Circuits 60H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 Code Enclosure Rating Material Size Enclosure Mounting 1 NEMA 4 Painted Steel Size is per design selection Wall-Mount Enclosure 2 NEMA 4X 304 SS 24 x 24 x 12 Wall-Mount Enclosure 3 NEMA 4X 304 SS 42 x 36 x 12 Wall-Mount Enclosure 4 NEMA 4X 304 SS 48 x 36 x 12 Wall-Mount Enclosure 5 NEMA 4X 304 SS 60 x 36 x 12 Wall-Mount Enclosure Code Enclosure Heater Class 1, Div 2 0 No Enclosure Heater 1 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater) For use with 6 & 12 circuit designs 2 Thermostat Controlled Enclosure Heater (to 0F Ambient) For use with 6 & 12 circuit designs 3 Thermostat Controlled Enclosure Heater (to -40F Ambient) For use with 6 & 12 circuit designs 4 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater For use with 18, 24, 30 & 36 circuit designs 5 Thermostat Controlled Enclosure Heater (to 0F Ambient) For use with 18, 24, 30 & 36 circuit designs 6 Thermostat Controlled Enclosure Heater (to -40F Ambient) For use with 18, 24, 30 & 36 circuit designs Code Inputs/Circuit I/O Mapping 0 1 No I/O Mapping 1 1 Full I/O Mapping 2 2 Full I/O Mapping 3 3 Full I/O Mapping 9 X Special Configuration ITLSC1D2-EXT - 24 1 4 3 Typical Model Number ** This code MUST match the same code on the base ITLSC1D2 Panel Technical Notes 1. 120-264V customer supplied instrument power supply 2. Our standard SCCR is 5 KA. Consult sales if a different SCCR is needed. 3. Do Not Exceed 80% of Panelboard Rating 4. These Extension Panels are to be paired with an ITLSC1D2 Panel. 34

38 Spare / Replacement Parts Model Number Note: Xxxx indicates that the design has varied from the order table Part parameters. This could include one or more of the following non- Number Item Description standard considerations: special software or configuration, private 0135-02261 SSR/GFI Power Control Assy., with Heat Sink branding, remote monitoring/touch-screen computer, sunshield or other protective covering, third party approval, floor stands, mount- 0135-02262 RTD Sensor Input Board Assembly ing options, special materials (316 SS) or coatings, additional vent- 0135-02263 Digital Distribution Comm Board Assembly ing or cooling, special indication or alarms. 0002-60054 SSR, 40 Amp rated 0029-00640 SSR Thermstrate Material Technical Notes 0025-05227 Common Alarm Relay 1. 120-264V customer supplied instrument power supply. 2. Standard SCCR is 5 KA. Consult sales if different SCCR is needed. 0081-10063 Power Supply 5VDC 6A 30W DIN Rail Mount 3. Do Not Exceed 80% of Panelboard Rating. 0081-10047 Power Supply 24VDC 2.5A 60W DIN Rail Mount 4. These extension panels are to be paired with an ITLSC1D2 Panel. ITLSC1D2 & ITLSC1D2-EXT I/O Mapping: Accessories Enclosure Size Part Enclosure Size H x W x D, In. (cm) Number Item Description 2 Inputs per 3 Inputs per Consult Factory Power Transformers Circuits Output Output 317315 RTD, Aluminum, NEMA 4, Pipe Mount 06 24x24x12 (61x61x31) 24x24x12 (61x61x31) 317340 RTD, Expl. Resist., NEMA 4, Pipe Mount 12 24x24x12 (61x61x31) 24x24x12 (61x61x31) 308056 RTD, Snap Lid, Alum, Ambient Sensing 308144 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 50 FT 18 42x36x12 (107x92x31) 42x36x12 (107x92x31) 317342 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 200 FT 24 42x36x12 (107x92x31) 48x36x12 (122x92x31) 0076-12009 Floor Stand Kit, 12 Deep, Steel 30 60x36x12 (152x92x31) Consult Sales 0076-12050 Floor Stand Kit, 12 Deep, 304 SS 36 60x36x12 (152x92x31) Consult Sales Consult Factory Floor Stand Kit, 12 Deep, 316 SS Total Number of Available Inputs per Panel Design Inputs / Circuit Code from Order Tables CE Third Party Compliance Circuits 1 2 3 Base Panel Model Number Instructions 06 06 12 18 ITLSC1D2-EXT-06 Add -CEXX suffix to Model Number 12 12 24 36 ITLSC1D2-EXT-12 Add -CEXX suffix to Model Number 18 18 36 54 ITLSC1D2-EXT-18 Add -CEXX suffix to Model Number 24 24 48 72 ITLSC1D2-EXT-24 Add -CEXX suffix to Model Number 30 30 60 Consult Sales ITLSC1D2-EXT-30 Add -CEXX suffix to Model Number 36 36 72 Consult Sales ITLSC1D2-EXT-36 Add -CEXX suffix to Model Number I/O Mapping Notes 1. The MAXIMUM number of Inputs for any ITLSC1D2 System, in- cluding Extension Panel, is 72. 2. When Full I/O Mapping is selected from the Order Table, any in- dividual sensor or output may be mapped to moren than one circuit. For Example: The average temperature of Sensors 1, 2 & 3 is used to control Circuit 1 while simultaneously the maximum temperature of Sensors 3, 4 & 5 is used to control Circuit 2. 35

39 ITASC1D2 Ambient Sensing, Class I, Division 2 6 36 Loops, Hazardous Environment (Class I, Div 2) ITASC1D2 ITASC1D2 Series Intelligent Ambient Sensing Heat Trace Panel. Designed for industrial applications and suitable for Class I, Division 2 Hazardous Areas. The ITASC1D2 series offers the following standard features: NEMA 4 enclosure, industrial 12 (30 cm) digital CE computer touchscreen operator interface, PID SCR power controller rated at 40A per circuit at 104F (40C) ambient, six to thirty-six circuits (expandable to seventy-two circuits*), common alarm output, hand/ off/auto operation, current monitoring, 30 mA ground fault equipment protection, RS485 ModBus / ethernet communications, remote monitoring capability, selectable soft start operation, UL & cUL third party compliance. Options include: NEMA 4XSS enclosure, wireless ethernet communications & ce certification Code Circuits Enclosure Size Line Voltage Line Phase Cable Voltage 06 6 Circuits 24H x 24W x 12D 120/208/240/277/480 1 120/208/240/277/480 12 12 Circuits 24H x 24W x 12D 120/208/240/277/480 1 120/208/240/277/480 18 18 Circuits 42H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 24 24 Circuits 42H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 30 30 Circuits 60H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 36 36 Circuits 60H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 Code Enclosure Rating Material Size Enclosure Mounting 1 NEMA 4 Painted Steel Size is per design selection Wall-Mount Enclosure 2 NEMA 4X 304 SS 24 x 24 x 12 Wall-Mount Enclosure 3 NEMA 4X 304 SS 42 x 36 x 12 Wall-Mount Enclosure 4 NEMA 4X 304 SS 48 x 36 x 12 Wall-Mount Enclosure 5 NEMA 4X 304 SS 60 x 36 x 12 Wall-Mount Enclosure Code Enclosure Heater Class 1, Div 2 0 No Enclosure Heater 1 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater) For use with 6 & 12 circuit designs 2 Thermostat Controlled Enclosure Heater (to 0F Ambient) For use with 6 & 12 circuit designs 3 Thermostat Controlled Enclosure Heater (to -40F Ambient) For use with 6 & 12 circuit designs 4 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater For use with 18, 24, 30 & 36 circuit designs 5 Thermostat Controlled Enclosure Heater (to 0F Ambient) For use with 18, 24, 30 & 36 circuit designs 6 Thermostat Controlled Enclosure Heater (to -40F Ambient) For use with 18, 24, 30 & 36 circuit designs Code Input Options 0 1 Standard Sensor Input 9 X Special Configuration CodeCommunications 0 Standard: RS485 ModBus/RTU or Wired Ethernet 9 Other CodeMonitoring 0 Standard Monitoring (Local HMI Only) 1 Remote Desktop (Wired/Wireless Ethernet Only) 9 Other Consult Sales ITASC1D2 - 24 1 4 0 - 0 1 Typical Model Number *42 - 72 circuit service via ITASC1D2-EXT Extension Panel. See ITASC1D2-EXT Heat Tracing Extension Panel - Ambient Sensing - Class 1, Division 2 order table Technical Notes 1. 120-264V customer supplied instrument power supply 2. Our standard SCCR is 5 KA. Consult sales if a different SCCR is needed. 3. Do Not Exceed 80% of Panelboard Rating 4. See ITASC1D2-EXT Extension Panel Order Table to increase total circuits 36

40 Spare / Replacement Parts CE Third Party Compliance Part Number Item Description Base Panel Model Number Instructions ITASC1D2-06 Add -CEXX suffix to Model Number 0135-02261 SSR/GFI Power Control Assy., with Heat Sink 0135-02262 RTD Sensor Input Board Assembly ITASC1D2-12 Add -CEXX suffix to Model Number 0135-02263 Digital Distribution Comm Board Assembly ITASC1D2-18 Add -CEXX suffix to Model Number 0002-60054 SSR, 40 Amp rated ITASC1D2-24 Add -CEXX suffix to Model Number 0029-00640 SSR Thermstrate Material ITASC1D2-30 Add -CEXX suffix to Model Number 0025-05227 Common Alarm Relay ITASC1D2-36 Add -CEXX suffix to Model Number 0081-10063 Power Supply 5VDC 6A 30W DIN Rail Mount 0081-10047 Power Supply 24VDC 2.5A 60W DIN Rail Mount Model Number Note: 0135-30490 ITASC1D2 HMI 12 diagonal programmed Xxxx indicates that the design has varied from the order table parameters. This could include one or more of the following non- standard considerations: special software or configuration, private branding, remote monitoring/touch-screen computer, sunshield or Accessories other protective covering, third party approval, floor stands, mount- ing options, special materials (316 SS) or coatings, additional venting Part or cooling, special indication or alarms. Number Item Description Consult Factory Power Transformers Technical Notes 317315 RTD, Aluminum, NEMA 4, Pipe Mount 1. 120-264V customer supplied instrument power supply. 2. Standard SCCR is 5 KA. Consult sales if different SCCR is needed. 317340 RTD, Expl. Resist., NEMA 4, Pipe Mount 3. Do Not Exceed 80% of Panelboard Rating. 308056 RTD, Snap Lid, Alum, Ambient Sensing 4. See ITASC1D2-EXT Extension Panel Order Table to increase total 308144 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 50 FT circuits. 317342 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 200 FT 0076-12009 Floor Stand Kit, 12 Deep, Steel 0076-12050 Floor Stand Kit, 12 Deep, 304 SS Consult Factory Floor Stand Kit, 12 Deep, 316 SS 37

41 ITASC1D2-EXT Extender Panel for the ITASC1D2, Class I, Div 2 (Add up to 36 additional Loops of Service) ITASC1D2-EXT ITASC1D2-EXT Series Intelligent Ambient Sensing Heat Trace Extension Panel. Designed for industrial applications and suitable for class I, division 2 hazardous areas. Designed to be used with ITASC1D2 heat trace line sensing panel to increase circuit service. ITASC1D2-EXT series offers the following standard features: NEMA 4 enclosure, PID SCR power controller rated at 40A per circuit at 104F (40C) ambient, six to thirty-six circuits, common alarm output, hand/off/auto operation, current monitoring, 30 mA ground fault equipment protection, RS485 modbus ethernet communications, UL & cUL third party compliance. Options include: NEMA 4XSS enclosure, thermostat controlled enclosure heater, remote monitoring capability, ce certification Code Circuits Enclosure Size Line Voltage Line PhaseCable Voltage 06 6 Circuits 24H x 24W x 12D 120/208/240/277/480 1 120/208/240/277/480 12 12 Circuits 24H x 24W x 12D 120/208/240/277/480 1 120/208/240/277/480 18 18 Circuits 42H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 24 24 Circuits 42H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 30 30 Circuits 60H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 36 36 Circuits 60H x 36W x 12D 120/208/240/277/480 1 120/208/240/277/480 Code Enclosure Rating Material Size Enclosure Mounting 1 NEMA 4 Painted Steel Size is per design selection Wall-Mount Enclosure 2 NEMA 4X 304 SS 24 x 24 x 12 Wall-Mount Enclosure 3 NEMA 4X 304 SS 42 x 36 x 12 Wall-Mount Enclosure 4 NEMA 4X 304 SS 48 x 36 x 12 Wall-Mount Enclosure 5 NEMA 4X 304 SS 60 x 36 x 12 Wall-Mount Enclosure Code Enclosure Heater Class 1, Div 2 0 No Enclosure Heater 1 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater) For use with 6 & 12 circuit designs 2 Thermostat Controlled Enclosure Heater (to 0F Ambient) For use with 6 & 12 circuit designs 3 Thermostat Controlled Enclosure Heater (to -40F Ambient) For use with 6 & 12 circuit designs 4 Thermostat Controlled Enclosure Heater (Anti-Condensation Heater For use with 18, 24, 30 & 36 circuit designs 5 Thermostat Controlled Enclosure Heater (to 0F Ambient) For use with 18, 24, 30 & 36 circuit designs 6 Thermostat Controlled Enclosure Heater (to -40F Ambient) For use with 18, 24, 30 & 36 circuit designs ITASC1D2-EXT - 24 1 4 Typical Model Number Technical Notes 1. 120-264V customer supplied instrument power supply 2. Our standard SCCR is 5 KA. Consult sales if a different SCCR is needed. 3. Do Not Exceed 80% of Panelboard Rating 4. These Extension Panels are to be paired with an ITASC1D2 Panel. 38

42 Spare / Replacement Parts CE Third Party Compliance Part Base Panel Model Number Instructions Number Item Description ITASC1D2-06 Add -CEXX suffix to Model Number 0135-02261 SSR/GFI Power Control Assy., with Heat Sink 0135-02262 RTD Sensor Input Board Assembly ITASC1D2-12 Add -CEXX suffix to Model Number 0135-02263 Digital Distribution Comm Board Assembly ITASC1D2-18 Add -CEXX suffix to Model Number 0002-60054 SSR, 40 Amp rated ITASC1D2-24 Add -CEXX suffix to Model Number 0029-00640 SSR Thermstrate Material ITASC1D2-30 Add -CEXX suffix to Model Number 0025-05227 Common Alarm Relay ITASC1D2-36 Add -CEXX suffix to Model Number 0081-10063 Power Supply 5VDC 6A 30W DIN Rail Mount 0081-10047 Power Supply 24VDC 2.5A 60W DIN Rail Mount Model Number Note: Xxxx indicates that the design has varied from the order table parameters. This could include one or more of the following non- standard considerations: special software or configuration, private branding, remote monitoring/touch-screen computer, sunshield or Accessories other protective covering, third party approval, floor stands, mount- ing options, special materials (316 SS) or coatings, additional venting Part or cooling, special indication or alarms. Number Item Description Consult Factory Power Transformers Technical Notes 317315 RTD, Aluminum, NEMA 4, Pipe Mount 1. 120-264V customer supplied instrument power supply. 2. Standard SCCR is 5 KA. Consult sales if different SCCR is needed. 317340 RTD, Expl. Resist., NEMA 4, Pipe Mount 3. Do Not Exceed 80% of panelboard rating. 308056 RTD, Snap Lid, Alum, Ambient Sensing 4. These extention panels are to be paired with an ITASC1D2 Panel. 308144 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 50 FT 317342 RTD Ext Wire, 3-wire, 16 ga, Cu, Shielded, 200 FT 0076-12009 Floor Stand Kit, 12 Deep, Steel 0076-12050 Floor Stand Kit, 12 Deep, 304 SS Consult Factory Floor Stand Kit, 12 Deep, 316 SS 39

43 ModBus Specification For complete communications specification details on ModBus messaging, Registers & I/O Mapping please refer to our ModBus Message Set Specification for Heat Trace Control Panel Communication manual. Limited Warranty: Please refer to the Chromalox limited warranty applicable to this product at http://www.chromalox.com/customer-service/policies/termsofsale.aspx. 1347 HEIL QUAKER BLVD., LAVERGNE, TN 37086 Phone: (615) 793-3900 www.chromalox.com 40 2013 Chromalox, Inc.

Load More